ODM D165T LV Moulded Case Pole Mounted Breaker Digital Trip Unit Suppliers, Factories

The D165T is a pole-mounted, molded-case circuit breaker engineered specifically for protecting distribution transformers on low-voltage overhead lines. This 4-pole breaker, rated at 165A and 440V, provides reliable protection against overloads, short-circuits, and phase imbalances. Housed in a weather-resistant fiberglass shell (IP31), it is built for outdoor operation from -25°C to 50°C. Featuring a digital trip unit, the D165T breaker can be precisely set to safeguard 50kVA, 100kVA, or 160kVA transformers. Its air-arc extinction technology ensures quick fault interruption, making this pole-mounted circuit breaker a robust and essential protection solution.

Product Description

Type Designation
LV Pole Mounted Circuit Breakers

The protection and management of MV/LV transformers in rural areas requires the use of specific circuit breakers adapted to significant load imbalances, and thus guarantees complete power usage even in unbalanced conditions. These devices (4 poles, three of which are protected) use air-break technology with chambers with metal partitions to cut the arc. Low voltage pole mounted circuit breaker D165T with a digital trip unit.

Technical Parameters
Parameters D165T D265T
Reference standard NH63-S-11 NH63-S-11
Voltage / Current Rating 440V / 165A 440V / 265A
Cutout / Closing Power 4000A / 6800A 6400A / 11700A
Poles / Outputs 4 Poles / 1 Output 4 Poles / 2 Outputs
Cable Sections 25/70mm*2 50/150mm*2
Breakdown Voltage (Pulse/Earth/Poles) 20KV / 10KV / 4KV 20KV / 10KV / 4KV
Control System / Installation Manual / On post Manual / On post
Product Display
Digital Trip Unit
LV Pole Mounted Breakers
Working Ambient
  • Temperature: -40°C ~ +70°C
  • Humidity: 100%
  • Altitude: ≤2000m
  • Wind speed: ≤40m/s

Note: No fire, no explosion hazards, no chemical corrosion and recurrent severe vibration.

Internal Structure Diagram
Internal Structure Diagram
  1. Incoming Wiring Clamp: Enables direct 4-phase power connection without crimping lugs.
  2. Incoming Wiring Hole: Provides cable access for both incoming and outgoing connections.
  3. Arc Chute Grid: User-replaceable component for effective arc extinguishing.
  4. Operation Mechanism: Spring-charged closing mechanism operable via floor-mounted handle.
  5. Digital Trip Unit: Configurable for 50/100/160 kVA with embedded current transformers.
  6. Load Indicator Trip: Orange indicator drops to trigger trip when load time is reached.
  7. Position Indicator: Green marker shows open/closed status through protrusion length.
  8. Operation Handle: Controls tripping (downward) and closing (upward) operations.
  9. Load Trip Enable/Disable Handle: Activates or deactivates the load trip function.
Outline and Installation Dimension
Outline Dimensions
FAQ
What are the primary applications for these pole mounted circuit breakers?
They are specifically designed for the protection and management of MV/LV transformers in rural areas, especially where significant load imbalances occur.
What kind of arc extinguishing technology is used?
The devices utilize air-break technology featuring chambers with metal partitions (arc chute grids) to effectively extinguish the arc.
Are these circuit breakers suitable for extreme weather conditions?
Yes, they are designed to operate in temperatures ranging from -40°C to +70°C and can withstand 100% humidity and wind speeds up to 40m/s.
How is the circuit breaker operated?
It features a manual spring-charged operation mechanism that can be controlled via a floor-mounted handle.
What is the advantage of the digital trip unit?
The digital trip unit is configurable for different capacities (50/100/160 kVA) and includes embedded current transformers for precise protection.
How many poles are protected in this 4-pole device?
The device has 4 poles in total, three of which are fully protected to ensure safety even in unbalanced load conditions.